Bonus Question:

A Power station has three section Busbars with 11 KV generators on the ring system as under:

Section 1
: Two Generators of 30 MVA & 20 MVA with 0.15pu
 & 0.12pu reactance respectively.

Section 2: One Generator of 60 MVA and 0.2pu
 reactance

Section 3: Two Generators of 30 MVA & 60 MVA with 0.18pu
 & 0.2pu reactance respectively.

Sections 1 & 2, 2 &3, 3 & 1 are connected through reactors of rating 60 MVA,90 MVA & 80 MVA with reactance 0.2pu, 0.3pu, 0.24pu
 respectively. 


  1. Determine the fault Current when a 3 -phase Symmetrical fault occurs at the far end of the feeder with a 0.05pu reactance & 0.01pu resistance on 30 MVA base, connected to Section number Three.
  2. Calculate the current Supplied by 60 MVA Generator  on section 3 bus under fault condition.









Answer:
  1. 17800 A
  2. 6760 A

For Solution Click Here